Heating planner
Answer a few questions about the building and see the required output, the suitable systems and the estimated yearly heating cost. It takes about two minutes.
Step 1 of 9
What type of building do you want to heat?
How we calculate
- Required output
- The heated area multiplied by the specific heat load: 40–55 W/m² for new builds, 70–90 W/m² for renovated buildings and 100–130 W/m² for old, uninsulated buildings. Hotels and guesthouses add 0.5 kW per guest for hot water.
- Yearly heat demand
- The output multiplied by the full-load hours: 2,000 hours a year for homes, 1,200–1,400 hours for commercial buildings, depending on use. Hot water for guests is calculated separately, from 30–40 litres per person per day.
- Yearly cost
- The yearly demand divided by the efficiency and multiplied by the energy price, at indicative values from October 2026: wood chips 0.15 RON/kWh, pellets 0.32 RON/kWh, logs 0.25 RON/kWh, electricity 1.30 RON/kWh; gas 0.31 RON/kWh for households and 0.44 RON/kWh for companies, used only for the cost of your current heating. Prices include VAT. Efficiency 90% for pellet and wood chip boilers, 85% for log boilers; the heat pump with a seasonal performance factor of 3.5. Energy cost only, without investment and maintenance; for logs, the work of preparing the wood and loading the boiler is not included.
- Buffer tank
- For biomass boilers we recommend 50 litres per kW of output, at least 30 litres per kW.